Backlinks Add to book Export to PDF Rename Page Book Creator Add this page to your book Book Creator Remove this page from your book Manage book (0 page(s)) Help S7 Recipe - Manager © by TIS Version 1.37 Recipe Management Since version 1.0.29.0 MobileHMI supports a recipe management: Several recipes, consisting of several date points, can be defined per page The entered data point values are saved to the recipe When the recipe is loaded, the stored date-point values are entered into the data points and can be sent to the PLC Recipe-Configuration HMI-Admin/Full Admin: Create, modify, delete recipes User: load recipe Recipe-Attribute: Produkt (assigned to an HMI page) Commission (Can be used for all HMI pages) Rezeptname In the HMI configuration, appears in the top bar to display the recipe menu: The following recipe list is displayed: Create / edit recipe Click in the main menu A new box will appear in each data point line Selected points are stored later in the recipe By clicking at the top of the recipe list, the recipe menu opens Select or re-enter the desired product, Commission and Recipe Saves or overwrites this recipe Load recipe Recipes are also loaded via the recipe manager Click on in the recipe menu Select the desired recipe from the three lists Click on to store the stored data in the respective DPs When you click on , all recipe data are transferred to the PLC Examples: View: HMI-Konfiguration Current recipe: light / heating Light / heating day mode Changing in light / heating Light / heating Night mode: In the HMI configuration, the stored data points are automatically marked in the recipe and the stored values are set. Ansicht: Benutzer The currently treated data points are marked with a dot. General S7 MOBILE HMI © by TIS Version 1.35 SPS-Types S7-1500 S7-1200 S7-300/400 with TCP/IP on Board / PN or CP 343-x/443-x S7-300/400 MPI/Profibus with S7-LAN Win AC RTX S7-200 with CP 243-1 S7-Soft-PLC SIMATIC-S5 over S5-LAN Operating systems Windows 10 8 7 Windows Server 2012 R2 2012 2008 R2 2008 Functions overview Visualization / control via web browser / mobile device (optional) OPC-UA-Server possible User account control Automatically generating the display To define your own scaling Areas of application Visualisation Control Data transfer via OPC-UA Installation Start “S7 OPC UA & Mobile HMI Setup 1.0.36.0.exe”. The installation checks whether you have installed the required software packages. Deinstallation System Control → Programs and Features → S7 OPC UA & Mobile HMI → Uninstall Remove the folder where the configuration data is stored PLC - Settings S7-1200/1500 The optimized block access needs to be deactivated in the data block attributes for access to the S7-1500 and S7-1200. In the S7-1500 must be enabled in the communication setting in addition to the PUT / GET access . How this works you see here (snapshot from TIA Portal) . LOGO! 1. Use the Logo Soft Comfort the IP address of a logo! PLCs: 2. Configure PLCs so that connections from an HMI device accepted the Logo!. To do so, go to “Tools- > Ethernet Connections” and then add a new connection. 3. Double-click on the newly created connection to access the properties. Select: Server Connection Local TSAP: 02:00 - 02:00 decentralized TSAP accept all connections. You can access DB1, inputs , outputs, flags , counters and timers with IP -S7 -LINK . Now put on “ Tools- > VM parameter map ” the variables that are to be transferred to the DB1. First Start After the start, you receive the following message: Select the location for the server data and click OK. You are then prompted to set the admin password: In the following start window, log in as admin and your chosen password: The application The application is divided into the menu and display area. Area of the menu Name Description call Start page ◄ one page backward ► one page forward Generate Machine Code, enter license key Call the server settings Information about the product and licensing Display area Displays the currently selected page with the available data and options. Im obigen Bild sehen Sie z.B. die Startseite. Fields marked with * are required. Configuration menu You can access all available pages by clicking on . The following menu items are available: Menu Description / task Home Call start page Benutzerverwaltung Manage your users and set permissible access to the data Verbindungen Establish the connections to your Siemens PLCs Datenpunkte Link the connections with the desired data addresses in the PLC. The tree structure allows you to pre-sort your data immediately Skalierungen Here you have the possibility to define various control and input elements for the view HMI-Config Design the desired view with main and sub-pages and add the desired data points to the respective data groups OPC-Konfiguration Sammelmenü für OPC-Einstellungen OPC-Server Create and manage OPC UA Server OPC-Client Zertifikate Certificates from OPC UA clients for the authenticated connection to the OPC UA server. You also assign the rights granted to the user Standard functions in the menu item: Funktion Task Add new settings Edit settings Delete settings User administration Overview of existing users. By clicking on a new user will be added and you get the following dialog: Name Function ID User-assigned ID Full Name Username is displayed Is Active User can log on Login Name Name zur Identifikation des Benutzers Password Password for login Admin Groups Assign to the desired admin group (s). See user group table User Groups Assignment to the desired user group (s). See user group table User group Function A1 Admin without restriction A2 OPC-Admin, Data points and OPC relevant data A3 HMI-Admin, Manage data points and HMI pages U1 - U8 User groups 1 to 8. User groups can be used to group multiple users. You can then assign different data points to this group, adapted to your requirements. For example: user group U1 = all layer leaders (sees all machines and can control them), U2 = machine operator H2 (only sees the machines in its task area) PLC-Connections Overview of configured Siemens PLC connections. Name Function ID System-assigned ID Name Name of the connection in the display IP-Adresse IP address under which the PLC can be reached Rack Rack number of the CPU Slot Slot of the CPU Gerätetyp Type designation of the PLC. Available types: Logo S7200 S7300_400 S71200 S71500 Connection type Default: Standard connection to the PLC (OperationPanel) OperationPanel: Connection via the OP channel ProgrammerDevice: Connection via the PG channel Other: Connection via the Other channel Connect Timeout Timeout in ms for connection setup Recieve Timeout Timeout in ms for receiving the data from the PLC Transmit Timeout Timeout in ms for sending to the PLC BreakDetection Timeout Keep Alive-Time for monitoring the TCP / IP connection (interesting at large intervals) User Break Detection Set Break Detection Timeout is used Ref Number of data points that point to this connection Data point definition The addresses of the data points, which serve as data sources, are defined here. The first node is always the connection. One connection can be added one New node New datapoint Name Description Left Adds a new node under the selected node Right Add a datapoint Rename the selected point Delete the selected point Name Description ID System-assigned ID Name Display name of the data point. If empty, the Data address (without spaces) is used as name. Verbindung Is added to this connection (the connection must already have been created) Adresse Data address to be processed in the PLC. DB1.DBB 0 for data block 1, data byte 0 Datentyp Specifies the data type that the software driver reads from the PLC Arraylänge Length of the array to be read Anzahl der zu erstellenden, konsekutive DPs Several consecutive data points can be created automatically. If the number is greater than 1, the end address of a data point is calculated and the address is entered as the next data point. Example: Name: Temperature, Address: DBW100.DBD10 , Type: Int16 , Number: 3 Generated: Name: Temperature_1 Address: DBW100.DBD10 Name: Temperature_2 Address: DBW100.DBD12 Name: Temperature_3 Address: DBW100.DBD14 Aktualisierungsintervall (ms) Time grid of data updating Nur lesen Data can only be read. Even if this is entered as a setpoint in the GUI, this DP can not be written anymore Ist Aktiv Data point can be used Ref Number of references used Move sample data points: beispiel_datenpunkt_verschieben.mp4 PLC address variables: Operand Name Abbreviation (Siemens, DE) Abbreviation(IEC) Input E I Output A Q Flag M M Peripherals P P Counter Z C Data Block DB DB Timer T 16 Data types Name Abbreviation Bit size Range Description Array BOOL X 1 0 to 1 single bit representing true (1) or false (0) x BYTE B 8 0 to 255 unsigned 8-bit x WORD W 16 0 to 65.535 unsigned 16-bit (Word) x DWORD D 32 0 to 232 -1 unsigned 32-bit (Double Word) x CHAR B 8 A+00 to A+ff ASCII-Code unsigned 8-bit character x INT W 16 -32.768 to 32.767 signed 16-bit integer x DINT D 32 -231 to 231-1 signed 32-bit integer (Double Word) x REAL D 32 +-1.5e-45 to +-3.4e38 IEEE754 32-bit single precision floating point number x S5TIME W 16 00.00:00:00.100 to 00.02:46:30.000 binary coded decimal (BCD) number representing a time span TIME D 32 00.00:00:00.000 to 24.20:31:23.647 signed 16-bit integer representing a time span in milliseconds TIME_OF_DAY D 32 00.00:00:00.000 to 00.23:59:59.999 unsigned 16-bit integer representing a time span in milliseconds DATE W 16 01.01.1990 to 31.12.2168 unsigned 16-bit integer representing a date in days DATE_AND_TIME D 64 00:00:00.000 01.01.1990 to 23:59:59.999 31.12.2089 binary coded decimal (BCD) number representing a date and time S7String B any A+00 to A+ff ASCII-Code, max. 254 Bytes The variables are composed of operand and data type. Examples: Examples Data type Example Siemens Example IEC Input Byte 1, Bit 0 BOOL E 1.0 I 1.0 Output Byte 1, Bit 7 BOOL A 1.7 Q 1.7 Flag Byte 10, Bit 1 BOOL M 10.1 M 10.1 Data Block 1, Byte 1, Bit 0 BOOL DB1.DBX 1.0 DB1.DBX 1.0 Input Byte 1 BYTE EB 1 IB 1 Output Byte 10 BYTE AB 10 QB 10 Flag Byte 100 BYTE MB 100 MB 100 Peripherals Input Byte 0 BYTE PEB 0 PIB 0 Peripherals Output Byte 1 BYTE PAB 1 PQB 1 Data Block 1, Byte 1 BYTE DB1.DBB 1 DB1.DBB 1 Data Block 1, Data Block 1 Typ bool, Address 1.0 → DB1.DBX 1.0 Data Block 1, Data Block Typ Byte, Address 1 → DB1.DBB 1 Peripherals Input, Typ DWORD, Address 0 → PED 0 Help: DB#.DBB # = Data Block#.Data Block Byte # DB#.DBW # = Data Block#.Data Block Word # DB#.DBD # = Data Block#.Data Block Doubleword # # = Address Service settings Among You will find the settings for the service. Service not installed: Service installed: Name Description HTTP Port Port for the web interface of the configuration / display Install + Start Service Installs the application as a service and starts it automatically Start manual start teh service Stop Stop the service, e.g. for changes Uninstall Service Remove the installed service If you want to change the port, stop the service and make the desired change and restart it. For external users to access the application, the following firewall rules must be added: Under Service set port If necessary, set OPC Server Ports Home Visualization start On the start page, you have the option to view the configured data. General information is also displayed. Scaling A scaling indicates how a “raw” data value (for example, number from the PLC) is converted into a representation (step text, numerical scaling, etc.). A combination of DP definition and normalization can then be used in the GUI as a set or actual value in a line. If no scaling is selected, a standard scaling is automatically used. During the initial installation, a switch and a button are automatically created. Name Importance Name Display name of scaling Scaling Select the type of display Text/String Display of a string data block as text Level text Allows the assignment of texts to values Linear Value is scaled metric Input type Specifies the type of control that is used for input. The following settings depend on the type of scaling Text field Is used with text / string. The data is provided in an input field Selection field or switch / button If two step texts have been entered, it is possible to create a switch / push button. To create a switch, initialize the value for the “On” state A push button is a switch with extended function. As soon as this is pressed, the following actions are carried out: * The “On” value is written to the PLC. * Waiting as long as the pulse duration has been specified. * The “Off value” is written to the PLC If more than 2 texts are entered, a selection field is automatically created Numeric text field Only numbers can be displayed and entered Slider A slider with the defined definitions is created in the display Ref This field is used to determine how often this data point is used in GUI lines Create selection field Enter a name Under Scale, select “Stufentext” Select Entry Type “Auswahlfeld oder Schalter/Taster” Add a new selection by clicking on The text is displayed in the visualization and the entered value is set in the PLC Example view: Create Switch Enter a name Under Scale, select “Stufentext” Select Entry Type “Auswahlfeld oder Schalter/Taster” You add two texts with values to the lower-level text Under “Schalter: Value state “On” enter the desired value Example view: Create Button Proceed as for the switch Under “Impulsdauer …” enter the time in ms, which the button should wait until the action is inverted Example view: Create a numeric field Enter a name Under Scale, select “Linear” Select Input type “Numerisches Textfeld” SPS Wert 1/HMI Wert 1 - A value that is in the PLC and is to be converted to the actual value Example: PLC 5 ≈ HMI Value 9 SPS Wert 2/HMI Wert 2 - A further value that is in the PLC and is to be converted. PLC / HMI value 1/2 must not have the same values Example: PLC 200 ≈ HMI value 90 The following information is optional: Name Description Min Ist The indicator will turn red if the value is out of range Max Ist The indicator will turn red if the value is out of range Min Soll Smallest value that can be entered Max Soll Greatest value that can be entered Schrittweite If specified, it is checked whether the value is not only in the predetermined value range but is also a desired permissible value. In these example settings, e.g. The values 1, 2, 3, 4 and values> 500 are not allowed Formatierung Formate the readout value according to predefined patterns. Example: “0.00 ##” ( Important: Always specify a point , no comma as decimal separator!) “0” = digit which is always displayed (0 if it does not occur) ”#“ = number which is only displayed if it actually occurs For “0.0 #”, the value 1 is displayed as “1.0” and 1.2345 is displayed as “1.23” Einheit [Deutsch] Characters added to the value. “° C”. In ”[]“ is the display language Example view: Create slider Enter a name Under Scale, select “Linear” Select Input type “Schieberegler” SPS Wert 1/HMI Wert 1 - A value that is in the PLC and is to be converted to the actual value SPS Wert 2/HMI Wert 2 - A further value that is in the PLC stands and is to be converted. PLC / HMI value 1/2 must not have the same values Enter the Min Set and Max Setpoint Name Description Min Ist The indicator will turn red if the value is out of range Max Ist The indicator will turn red if the value is out of range Min Soll Smallest value that can be selected Max Soll Greatest value that can be selected Schrittweite Automatically calculates the next permitted value. In these example settings, e.g. Only select values 5, 5.5 to 30 in increments of 0.5 Formatierung Form the value read out according to predefined patterns. Example: “0.00 ##” ( Important: Always specify a point , no comma as decimal separator!) “0” = digit, which is always displayed (0 if it does not occur) ”#“ = number that is only displayed if it actually occurs) For “0.0 #”, the value 1 is displayed as “1.0” and 1.2345 “is displayed as “1.23” Einheit [Deutsch] Characters added to the value. “° C” In ”[]” is the display language Example view: HMI-Config Here you configure the view of your application. Name/Symbol Description Opens the menu Back to the start page Edit the page. Here, for example, Change the title Automatic generation of the HMI view Create new page Create data point group. Here you enter the title of the group and have the following options: Apply setpoint changes immediately Data is immediately transferred to the PLC Frameless group Changes are accepted immediately and data points are displayed directly on the main page. The group heading is omitted Selected data group(s), page(s) and data point(s) in the respective direction Start page Title of the current page Online = Data is read and written live from the data source. Offline = Data is simulated Log out user For each page / group, a toolbar is displayed. In this bar you can edit the settings and the position. There is a special display area for the push-button. The selected data point is used for the display. Example : A light button is pressed The light is switched on The state of the light is stored in a flag If the state data point is selected for the display, this address is displayed and not the defined action texts. beispielanzeigetext.mp4 Seite erstellen Example video: beispiel_seiten_anlegen.mp4 beispiel_seiten_anlegen2.mp4 Click . The following dialog opens: Enter the desired title. After confirmation, the toolbar appears next to the page. Symbol Description Select page for move Edit page properties eg Edit title Deletes the page with all subpages and data groups Title of the page. Click to open it One page is used to optically delimit groups of data points. With a frameless group it is also possible to display data points without a heading in the page. Example : View frameless group in configuration User view View normal data group in the configuration User view Create automatically You have the possibility to automatically generate the view by clicking on on the basis of all created data points. All unused data points are automatically marked. When the interfaces are selected, a page or data group with the data points is automatically created when you create it. Assign data point To add data points, you need a data point group. With you can generate a new group: Option Function Titel Title Sollwert-Änderungen sofort übernehmen Changes are written directly to the PLC Rahmenlose Gruppe Data points are displayed directly on the page You should see the following: With you can create a new data point: Enter the name for the data point Select the previously defined data point for the desired range Select the previously defined scale Confirm with “Save” the settings and see immediately the result You can also define a Min and Max value for the display. As soon as one of these limits is exceeded, the display shows this value red. If you have defined a data array as a data point, you must specify the desired array index. Assign multiple data points In order not to have to create all data areas individually, it is possible to generate them automatically. Click on . Folowing dialog is been shown: All previously unused data points are selected automatically. Option Description Titel[de] The entered data point name is not used automatically. If something is entered and several data points are automatically appended “_ #” (# = incremented number) Istwert-Datenpunkt Yes = Data point Actual value is displayed before the input field Istwert-Skalierung Value is displayed using the previously defined scale, if nothing is selected, the field is given a default format Sollwert-Datenpunkt Yes = Data point Setpoint is displayed before the input field Sollwert-Skalierung Value is displayed using the previously defined scale, if nothing is selected, the field is given a default format Taster Anzeigewert-Datenpunkt Data point to be displayed Taster Anzeigewert-Skalierung Applied scaling on the button After saving, you will see the created data points and can modify them. Examples: Data point Example Service settings Among You will find the settings for the service. Service not installed: Service installed: Name Description HTTP Port Port for the web interface of the configuration / display Install + Start Service Installs the application as a service and starts it automatically Start manual start teh service Stop Stop the service, e.g. for changes Uninstall Service Remove the installed service If you want to change the port, stop the service and make the desired change and restart it. For external users to access the application, the following firewall rules must be added: Under Service set port If necessary, set OPC Server Ports Change MobileHMI Theme With the Jquery Mobile Theme Roller. MobileHMI use Theme “A”. Proceed as follows: Edit Theme “A” Then click on “Download theme zip file” As name jquery.mobile.theme.custom (important for the file name of the created CSS file to be correct) Unzipped downloaded zip file Copy the contents of this folder “themes” to the “<HMI-Directory> \ custom-theme” folder Edit Icons Proceed as follows: In the “<HMI Directory> \ custom-theme” folder, create the “main.custom.css” file Create folders for image files, e.g. “Img” Change desired icons via script To change an icon, add the following lines to main.custom.css: .hmi-button-<Iconname>:after { background-image: url("/img/<Name-der-Icon-Datei>"); background-size: 90%; } Beispiel: /* Icon Home-Button ändern */ .hmi-button-home:after { background-image: url("/img/Mein-Bild.png"); background-size: 90%; } You can specify your own image files for the following icon names: Name Changes Control loginlogout Logout at the bottom left home Show Home back Page back (bottom left) forward Page forward (bottom left) autogenerate-hmi Automatic generation of data points and pages new-page Create page edit-page edit page delete-page Delete the page with all subpages and data points new-group Add data group edit-group Edit data group delete-group Delete data group with many data points move-pageelement-up Page(s), move data group(s) up move-pageelement-down Page(s), move data group(s) down move-pageelement-parent Page(s), data groups) to the desired page / group new-datapoint Create data point newmultiple-datapoint Several data points edit-datapoint Edit the data point delete-datapoint Delete the data point move-datapoint-up move data point(s) up move-datapoint-down move data point(s) down move-datapoint-parent move data point(s) into the desired group dp-submit-changes Transfer changes to the PLC dp-revert-changes Discard changes in the page dp-pushbutton-set Press the button of view dp-pushbutton-unset Button of view on release S7 OPC UA & MobileHMI Home Visualisierung start Benutzerverwaltung Name Login Name Passwort Benutzergruppe Admingruppen A1-A3 Benutzergruppen U1-U8 Verbindungen Name IP-Adresse Rack Slot Gerätetyp Logo S7200 S7300_400 S71200 S71500 Verbindungstyp Default Operation Panel Programmer Device Other Timeouts Connect Recieve Transmit BreakDetection Datenpunkte Verbindung(en) Datenpunkt(e) Knoten Datenpunkt(e) Unterknoten Datenpunkt(e) Name Adresse Datentyp Bool Byte UInt16 Int16 UInt32 Int32 UInt64 Int64 SingleFP (23 bit Mantisse, 8 bit Exponent, 1 bit Vorzeichen) DoubleFP (52 bit Mantisse, 11 bit Exponent, 1 bit Vorzeichen) String Arraylänge Anzahl der zu erstellenden, konsekutiven Datenpunkte Aktualisierungsintervall Nur lesen Skalierungen Name Skalierung Text/String Stufentext Linear Eingabeart Textfeld Numerisches Textfeld Schieberegler Auswahlfeld oder Schalter/Taster HMI-Config Seite(n) Datenpunktgruppe(n) Datenpunkt(e) Unterseite Datenpunktgruppe(n) Datenpunkt(e) Seite anlegen Titel Datenpunktgruppe anlegen Titel Datenpunkt zuweisen Titel Istwert-DP Istwert-Skalierung Sollwert-DP Sollwert-Skalierung Taster-Anzeigewert Taster-Skalierung Numerischer Istwert-Min Numerischer Istwert-Max OPC Server Alle Server neustarten Neuen Server anlegen Server Name Transport TCP HTTP Hostname Port URI Path Automatically create rejected user certificates Server Certificate User Access Everyone Acces URI Server starten Server stoppen Server neustarten OPC Client Zertifikate Name Is active Certificate File Admingruppe festlegen Benutzergruppe festlegen Recipe Manager Clear Selection Product Commission Recipe Rezept laden Recept speichern Table of Contents Recipe Management Recipe-Configuration Create / edit recipe Load recipe General SPS-Types Operating systems Functions overview Areas of application Installation Deinstallation PLC - Settings S7-1200/1500 LOGO! First Start The application Area of the menu Display area Configuration menu User administration PLC-Connections Data point definition Service settings Home Visualization start Scaling Create selection field Create Switch Create Button Create a numeric field Create slider HMI-Config Seite erstellen Create automatically Assign data point Assign multiple data points Service settings Change MobileHMI Theme Edit Icons